Diesel generator sets are the emergency standby power supply providers after the mains failure. Most of the time, the units are in standby standby state. Once the power failure occurs, the units are required to "start in urgent time, supply in urgent time", otherwise the standby units will lose significance. Practice has proved that: strengthening daily maintenance is the most economical and effective method, because the unit length is in static, the unit itself various materials will have complex chemical and physical changes with oil, cooling water, diesel, air, etc., so as to "stop" the unit.
1. Starting battery failure of the unit
Battery for a long time no maintenance, electrolyte moisture volatilization can not be timely replenishment, no configuration of starting battery charger, battery after a long time of natural discharge reduced, or the use of the charger needs to be manually charged regularly, due to negligence did not carry out the switching operation resulting in battery power cannot meet the requirements, in addition to the configuration of high-quality chargers, Necessary testing and maintenance is required.
2. Water enters the diesel engine
Due to the condensation of water in the air at the change of temperature, the formation of water beads attached to the inner wall of the tank, into diesel, resulting in excessive water content of diesel, such diesel into the engine high-pressure oil pump, will rust precision coupling parts ----- plunger, serious damage to the unit, regular maintenance is effectively avoided.
3. Oil retention period (two years)
The engine oil is mechanical lubrication, and the oil also has a certain retention period, a long time storage, the physical and chemical properties of the oil will change, resulting in the deterioration of the lubrication condition of the unit working, easy to cause damage to the unit parts, so the lubricating oil should be replaced regularly.
4, three filter replacement cycle (wood filter, machine filter, air filter, water filter)
Filter is to play the role of diesel oil, oil or water filtration, to prevent impurities into the body, and in the diesel oil oil, impurities are inevitable, so in the operation of the unit, the filter plays an important role, but at the same time these oil or impurities are deposited on the screen wall and filter capacity is reduced, deposition is too much, the oil circuit will not be smooth, In this way, when the oil machine is carrying, it will shock due to the inability to supply oil (like hypoxia), so the normal generator set in the process of use, we recommend: first, the common unit every 500 hours to replace the three filters; Second, the standby unit every two years to replace the three filter;
5. Cooling system
Water pump, water tank and water transmission pipe for a long time is not cleaned, so that the water circulation is not smooth, cooling effect decreases, whether the water pipe joint is good, water tank, water channel is leaking, if the cooling system has a fault, the consequences are: first, the cooling effect is not good and the water temperature in the unit is too high and shut down, Wellson unit is the most common; Second, the water tank leaks and the water level in the water tank drops, the unit will not work normally (in order to prevent the use of generators in winter, water pipe freezing, we suggest that it is best to install water heaters in the cooling system).
6, lubrication system, seals
Due to the chemical characteristics of lubricating oil or oil ester and the iron filings produced after mechanical wear, these not only reduce its lubrication effect, but also accelerate the damage of parts, at the same time because the lubricating oil has a certain corrosion effect on the rubber sealing ring, in addition to the oil seal itself is also at any time and aging to reduce its sealing effect.
7. Fuel and gas distribution system
Engine power output is mainly fuel combustion in the cylinder work and fuel is emitted through the nozzle, which makes the carbon deposit after combustion in the nozzle, with the increase of deposition amount of fuel injection nozzle will be affected to a certain extent, resulting in the nozzle ignition advance Angle time is not accurate, the amount of fuel injection of each cylinder of the engine is not uniform, the working state is not stable, So the regular cleaning of the fuel system, the replacement of the filter parts, the smooth oil supply, the adjustment of the distribution system to make its ignition uniform.
8. Control part of the unit
The control part of the oil machine is also an important part of unit maintenance. If the unit is used too long, the line joint is loose, and the AVR module works normally.
Jiangsu Meao Power Technology Co., Ltd. is an important manufacturer of diesel generators. The company mainly manufactures and sells diesel generator sets with power of 3-3000kW, mobile power station of 24-600kW, Marine emergency diesel generator set of 24-800kW, gas generator set, heavy oil generator set and all kinds of imported series, special series (trailer, static speaker, mobile lighthouse, container, etc.) diesel generator At the same time, we are engaged in generator set maintenance and after-sale service of generator set accessories.